48 Actual signals and parameters
START/STOP Reset along with the stop signal received through a
digital input, or from the control panel.
Note: Do not use this option when start, stop and
direction commands are received through fieldbus
communication.
7
COMM Fieldbus interface as the source for the fault reset
signal, that is the Control word 0301 FB CMD WORD
1 bit 4 (with ABB drives profile 5319 EFB PAR 19 bit 7)
(see ACS355 Users manual (3AUA0000066143
[English]). The Control word is sent by the fieldbus
controller through the fieldbus adapter or embedded
fieldbus (Modbus) to the drive. For the Control word
bits, see sections DCU communication profile and
ABB drives communication profile in ACS355 User’s
manual (3AUA0000066143 [English]).
8
DI1(INV) Reset through inverted digital input DI1 (reset on the
falling edge of DI1) or from the control panel
-1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
1606 LOCAL LOCK Disables entering local control mode or selects the
source for the local control mode lock signal. When the
local lock is active, entering the local control mode is
disabled (LOC/REM key of the panel).
DI2
NOT SEL Local control is allowed. 0
DI1 Local control mode lock signal through digital input
DI1. Rising edge of digital input DI1: Local control
disabled.
Failing edge of digital input DI1: Local control allowed.
1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
ON Local control is disabled. 7
All parameters
No. Name/
Value
Description Def/ FbEq