Actual signals and parameters 55
60 PUMP CONTROL
Defines pump control parameters.
6001 AUTO/MANUAL
SEL
Selects the start mode of the inverter. MANUAL
AUTO Inverter starts automatically if DC bus voltage is more
than the 6003 START DC VOLT.
Note: If the timed function is enabled in parameter
3601 TIMERS ENABLE, then the drive starts as per
the timed function configuration. For more details of
timed function, see group 36 TIMED FUNCTIONS in
ACS355 Users manual (3AUA0000066143 [English]).
0
MANUAL Inverter starts when the manual start command is on.
See parameter 6002 MANUAL START CMD.
1
6002 MANUAL
START CMD
Defines the source for inverter to start in manual
mode. The selection is effective when parameter 6001
is MANUAL and the inverter is in remote control mode.
DI1
DI1 Start and stop through digital input DI1.
0 = Stop, 1 = Start
0
DI2 Start and stop through digital input DI2.
0 = Stop, 1 = Start
1
DI3 Start and stop through digital input DI3.
0 = Stop, 1 = Start
2
DI1P, 2P Pulse starts through digital input DI1.
0 -> 1: Start.
Pulse stops through digital input DI2. 1 -> 0: Stop
Note: To start the inverter, activate DI2 prior to feeding
pulse to DI1.
3
6003 START DC
VOLT
Defines the minimum DC voltage to start the inverter.
Note: If you change this value while the inverter is
running, the changed value is effective only during the
next start.
1 = 1 V
109...800 V DC voltage.
Note: Range is different for 1-phase and 3-phase
inverters.
400 V unit:
225
200 V unit:
129
All parameters
No. Name/
Value
Description Def/ FbEq