54 Actual signals and parameters
30 FAULT
FUNCTIONS
Programmable protection functions
3010 STALL
FUNCTION
Selects how the drive reacts to a motor stall condition.
The protection is active if the drive has operated in a
stall region (see the figure below) longer than the time
set by parameter 3012 STALL TIME.
In vector control the user defined limit = 2017 MAX
TORQUE 1 / 2018 MAX TORQUE 2 (applies for
positive and negative torques). See ACS355 User’s
manual (3AUA0000066143 [English]).
In scalar control the user defined limit = 2003 MAX
CURRENT. See ACS355 User’s manual
(3AUA0000066143 [English]).
The control mode is selected by parameter 9904
MOTOR CTRL MODE.
FAULT
NOT SEL Protection is inactive. 0
FAULT The drive trips on fault MOTOR STALL (0012) and the
motor coasts to stop. See ACS355 Users manual
(3AUA0000066143 [English]).
1
ALARM The drive generates alarm MOTOR STALL (2012).
See ACS355 User’s manual (3AUA0000066143
[English]).
2
3011 STALL
FREQUENCY
Defines the frequency limit for stall function. See
parameter 3010 STALL FUNCTION.
10.0 Hz
0.5...50.0 Hz Frequency 1 = 0.1 Hz
3012 STALL TIME Defines the time for stall function. See parameter 3010
STALL FUNCTION.
10 s
10...400 s Time 1 = 1 s
3026 POWER FAIL
START
Selects how the drive reacts when the control board is
externally powered by the MPOW-01 auxiliary power
extension module (see Appendix: Extension modules
in ACS355 User’s manual (3AUA0000066143
[English]) and start is requested by the user.
Note: Only FAULT selection is available.
FAULT
FAULT The drive trips on fault 0006 DC UNDERVOLT (See
ACS355 User’s manual (3AUA0000066143 [English]).
2
All parameters
No. Name/
Value
Description Def/ FbEq