Actual signals and parameters 59
0...3276.0 kW Power 0
6102 PQ CURVE P2 Defines the input power of pump at point 2 on the PQ
curve.
10 = 1 kW
0...3276.0 kW Power 0
6103 PQ CURVE P3 Defines the input power of pump at point 3 on the PQ
curve.
10 = 1 kW
0...3276.0 kW Power 0
6104 PQ CURVE P4 Defines the input power of pump at point 4 on the PQ
curve.
10 = 1 kW
0...3276.0 kW Power 0
6105 PQ CURVE P5 Defines the input power of pump at point 5 on the PQ
curve.
10 = 1 kW
0...3276.0 kW Power 0
6111 PQ CURVE Q1 Defines the flow rate at point 1 on the PQ curve. 10 = 1 m³/h
0...3276.0 m³/h Flow rate 0
6112 PQ CURVE Q2 Defines the flow rate at point 2 on the PQ curve. 10 = 1 m³/h
0...3276.0 m³/h Flow rate 0
6113 PQ CURVE Q3 Defines the flow rate at point 3 on the PQ curve. 10 = 1 m³/h
0...3276.0 m³/h Flow rate 0
6114 PQ CURVE Q4 Defines the flow rate at point 4 on the PQ curve. 10 = 1 m³/h
0...3276.0 m³/h Flow rate 0
6115 PQ CURVE Q5 Defines the flow rate at point 5 on the PQ curve. 10 = 1 m³/h
0...3276.0 m³/h Flow rate 0
6121 PUMP
EFFICIENCY
Defines the total efficiency of the motor/pump
combination.
1 = 1%
0...100% Percentage 100%
6122 PUMP NOM
SPEED
Defines the nominal speed of pump. This value is used
for flow calculation in CALCULATED FLOW, see
page 37.
1 = 1 rpm
0...3000 rpm Speed 3000 rpm
6123 CALC LOW
SPEED
Defines the minimum speed limit below which flow is
not calculated.
1 = 1 rpm
100...3000 rpm Speed 500 rpm
All parameters
No. Name/
Value
Description Def/ FbEq

Table of Contents