58 Actual signals and parameters
6021 PMP CLEAN
SELECT
Enables the pump cleaning sequence for the inverter
in the manual mode (see 6001 AUTO/MANUAL SEL)
and defines the selection conditions.
WARNING! Before enabling the pump
cleaning sequence, make sure that it can be
performed safely with the connected
equipment.
Note: When the pump cleaning sequence is active, it
cannot be stopped with OFF selection. After the
cleaning sequence is completed successfully or if the
sequence is interrupted due to a fault, it automatically
switches to OFF selection.
OFF
OFF Disables pump cleaning sequence. 0
ON Enables pump cleaning sequence. 1
6022 PMP CLEAN
SPEED
Defines the speed at which the pump cleaning
sequence is initiated.
1 = 1 rpm
500...3000 Speed. 500 rpm
6023 PMP CLEAN
TIME
Defines the pump cleaning time for which the motor
rotates in one direction (forward or reverse) within
which the cleaning sequences are counted.
1 = 1 sec
1...300 Time 60 sec
61 FLOW
CALCULATION
Defines flow calculation parameters.
6101 PQ CURVE P1 Defines the input power of pump in kW at point 1 on
the PQ performance curve.
For description of PQ curve, see section Flow
calculation, page 33.
10 = 1 kW
All parameters
No. Name/
Value
Description Def/ FbEq
Q[m³/h]
6105
6101
6111
6115
P[kW]