Actual signals and parameters 57
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
DI1(INV) Inverted digital input DI1. Defines the inverted digital
input DI1 as the control for dry run protection.
6
DI2(INV) See selection DI1(INV).7
DI3(INV) See selection DI1(INV).8
DI4(INV) See selection DI1(INV).9
DI5(INV) See selection DI1(INV).10
WITH_P60.16 See parameter 6016 MIN LOAD CURRENT 11
6016 MIN LOAD
CURRENT
Defines the minimum load current for dry run
protection of inverter. When actual motor current is
less than this value for the time defined in 6017 DRY
RUN TRP TIME, the inverter trips due to DRY RUN.
1 = 1 A
0...2 * Drive
rating A
Current 0
6017 DRY RUN TRP
TIME
Allows inverter to wait for this time to trip if pump is in
dry run condition. See 6016 MIN LOAD CURRENT.
1 = 1 min
0...5 mins Time 2 mins
6018 DRY RUN RST
TIME
Allows inverter to wait for this time to reset in case of a
dry run fault. After this reset time, inverter starts
automatically.
1 = 1 min
2...300 mins Time 2 mins
6019 FAULT RESET
TIME
Allows inverter to wait for this time to restart
automatically in case inverter tripped due to under-
voltage fault, PV cell maximum voltage fault or when
actual speed decreased below the minimum motor
speed defined in 6006 PUMP MINIMUM SPD.
1 = 1 min
2...20 mins Time 2 mins
All parameters
No. Name/
Value
Description Def/ FbEq