DefaultUnitRange/ListNameIndex
NameBitNameBit
Timed function 32Timed function 10
Reserved04…15Timed function 21
Off[0]-0...7Boost time activation
source
34.111
Other...DI6[7]DI5[6]DI4[5]DI3[4]DI2[3]DI1[2]On[1]Off[0]
00:00:00-00 00:00…07 00:00Boost time duration34.112
35 Motor thermal protection
0°C-60…1000 °CMotor estimated temperat-
ure
35.01
0°C-60…5000 °CMeasured temperature 135.02
0°C,-60…5000 °CMeasured temperature 235.03
0.0%0.0...300.0%Motor overload level35.05
Estimated tem-
perature[1]
--Temperature 1 source35.11
PTC analog I/O [20]Direct temperature[11]Disabled[0]
Therm(0)[21]KTY83 analog I/O[12]Estimated temperature[1]
Therm(1)[22]1 × Pt1000 analog I/O[13]KTY84 analog I/O[2]
2 × Pt1000 analog I/O[14]1 × Pt100 analog I/O[5]
3 × Pt1000 analog I/O[15]2 × Pt100 analog I/O[6]
NI 1000[16]3 × Pt100 analog I/O[7]
PTC extension module[19]PTC DI6 [8]
130 °C°C-60…5000 °CTemperature 1 fault limit35.12
110 °C°C-60…5000 °CTemperature 1 warning limit35.13
Not selected[0]-0...2Temperature 1 AI source35.14
Other...AI2 actual value[2]AI1 actual value[1]Not selected[0]
Estimated tem-
perature[1]
-See parameter 35.11
Temperature 1 source
Temperature 2 source35.21