DefaultUnitRange/ListNameIndex
130 °C°C-60…5000 °CTemperature 2 fault limit35.22
110 °C°C-60…5000 °CTemperature 2 warning limit35.23
Not selected[0]-See parameter 35.14
Temperature 1 AI
source
Temperature 2 AI source35.24
20°C-60…100 °CMotor ambient temperature35.50
110%50…150Motor load curve35.51
70%25…150Zero speed load35.52
45.00Hz1.00 500.00Break point35.53
80°C0…300 °CMotor nominal temperature
rise
35.54
256s100…10000Motor thermal time con-
stant
35.55
Warning and
fault[2]
-No action[0], Warning
only[1], and Warning
and fault[2]
Motor overload action35.56
Class 20[2]-Class 5[0], Class 10[1],
Class 20[2], Class 30,[3]
Class 40[4]
Motor overload class35.57
36 Load analyzer
Motor current[4]--PVL signal source36.01
Process PID out[16]Speed ref ramp
out[11]
Motor torque[6]Not selected[0]
Other...Torque ref used[13]DC voltage[7]Motor speed
used[1]
Freq ref used[14]Output power[8]Output fre-
quency[3]
Reserved[15]Speed ref ramp
in[10]
Motor current[4]
2.00s0.00 120.00PVL filter time36.02
Done[0]-Done[0], PVL[2]Reset loggers36.09
0.00--32768.00 32767.00PVL peak value36.10
1/1/1980-1/1/1980...6/5/2159PVL peak date36.11
00:00:00-00:00:00...23:59:59PVL peak time36.12