Start-up and validation test
Contents of this chapter
This chapter describes the start-up, validation test procedure, and validation of the
safety function.
Validation of the safety functions
You must do a validation test to make sure that the safety function operates correctly
and according to the safety requirements.
Competence
The person who does the validation test of the safety function must be a competent
person with expertise and knowledge of the safety function and functional safety, as
required by IEC 61508-1 clause 6. This person must document and sign the test
procedures and report.
Validation procedure
You must do the validation test using the checklist given in this manual and the
validation test plan of the complete safety system:
at the initial start-up of the safety function
after changes related to the safety function (wiring, components, safety function
-related parameter settings, etc.)
after changes related to the power unit or its circuit boards
after maintenance work related to the safety function
at the proof test of the safety function.