The validation test must include at least the following steps:
you must have a validation test plan
you must test all commissioned functions for correct operation, from each
operation location
you must document all validation tests
you must sign and store the validation test report for further reference.
Validation test reports
You must store the signed validation test reports in the logbook of the machine. The
report must include, as required by the referred standards:
a description of the safety application (including a figure)
a description and revisions of safety components that are used in the safety
application
a list of all safety functions that are used in the safety application
a list of all safety-related parameters and their values
documentation of start-up activities, references to failure reports and resolution
of failures
the test results for each safety function, checksums, date of the tests, and
confirmation by the test personnel.
You must store any new validation test reports done due to changes or maintenance
in the logbook of the machine.
Start-up and validation test
You must use the Drive Composer PC tool or a control panel to do the start-up and
validation test.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
Initial status
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up
procedure. Refer to the hardware manual
Make sure that the STO function is configured and validated. Refer to the drive hardware manual.
Checks and settings with no voltage connected
Stop the drive and do the steps in section Electrical safety precautions (page 9) before you start
the work.
If you made connections to the emergency stop circuit on site (for example, added emergency
stop buttons), do a check of the connections against the applicable circuit diagrams.
Settings with voltage connected
Close the cabinet doors and power up the drive. Refer to the hardware manual.
26 Start-up and validation test