118 Option
Note: In case Marshalling PLC reports F002 PLC IO module fault, refresh Par16 PLC IO
refresh, to match actual IO modules. After refreshing, Marshalling PLC will reboot and be
configured to correct HW variants.
Customer interface
SBU marshalling PLC has 3 control sources: IOs control, Fieldbus control and Panel control.
1. IOs control source
From the PLC hardware configuration, below IO signals are defined for customer control
and monitoring. These command signals are available when Parameter 1 Control
source selects IOs.
Position Type Number Name
EMB CPU PM556-TP-ETH DI2 Reset
EMB CPU PM556-TP-ETH DO1 Fault
EMB P1 DI562 DI1 Motor 1 selection
EMB P1 DI562 DI2 Motor 2 selection
EMB P1 DI562 DI3 Motor 3 selection
EMB P1 DI562 DI4 Motor 4 selection
EMB P1 DI562 DI5 Motor 5 selection
EMB P1 DI562 DI6 Motor 6 selection
EMB P1 DI562 DI7 Motor 7 selection
EMB P1 DI562 DI8 Motor 8 selection
EMB P1 DI562 DI9 Motor 1 direct online
EMB P1 DI562 DI10 Motor 2 direct online
EMB P1 DI562 DI11 Motor 3 direct online
EMB P1 DI562 DI12 Motor 4 direct online
EMB P1 DI562 DI13 Motor 5 direct online