Standard Commissioning Process 33
2. Inform customer send MCB close/open status signal, and measure voltage as below
table, the values should not be higher than 5V.
MCB status drawing
Probe+ Probe- AC DC
X1:20 PE < 5V < 5V
X1:22 PE < 5V < 5V
X1:24 PE < 5V < 5V
X1:26 PE < 5V < 5V
X1:28 PE < 5V < 5V
X1:30 PE < 5V < 5V
PLC DI0 and DI1
F24V:5 and X24V1:4