Standard Commissioning Process 69
• Drive insulation test is not mandatory.
Setting parameters and checking control signals
• Switch on the control and auxiliary power supply accordingly. Return to Drive
composer, select Refresh in menu View, get into the online mode.
Note: Refresh and check the service access level once restarting the connection, enter
again the service level passcode if needed.
• Check the SW or firmware version.
Note: ACS-AP-W/S version should be checked also (folder \05_ControlPanel FW)
• Set the license received from the MV Drives Supportline. The Par. 96.70 license state
should be Time unlimited.
Note: The position of BCON series number is shown hereunder.
NOTICE Below information should be provided to MV Drives Supportline for license
inquiry:
• series number of the drive
• series number of the BCON board