Technical data 101
1) 50% overload is available for one minute every 5 minutes if ambient temperature is less than 25 °C
(77 °F). If ambient temperature is 40 °C (104 °F), max. available overload is 37%.
2) 50% overload is available for one minute every 5 minutes if ambient temperature is less than 30 °C
(86 °F). If ambient temperature is 40 °C (104 °F), max. available overload is 40%.
3) 50% overload is available one minute every 5 minutes if ambient temperature is less than 20 °C
(68 °F). If ambient temperature is 40 °C (104 °F), max. available overload is 30%.
4) 50% overload is available one minute every 5 minutes if ambient temperature is less than 35 °C
(95 °F). If ambient temperature is 40 °C (104 °F), max. available overload is 45%.
5) These values are not calculated according to the ecodesign standard IEC 61800-9-2.
*) Higher value applicable if output frequency is above 41 Hz.
Symbols
-0440-7 396 656 400 387 355 328 315 R8 1220 7400
-0490-7 445 775 450 426 400 387 355 R8 1220 8450
-0550-7 488 853 500 482 450 426 400 R8 1220 8300
-0610-7 560 964 560 537 500 482 450 R8 1220 9750
00096931
Nominal ratings
I
cont.max
continuous rms output current. No overload capability at 40 °C (104 °F).
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by
drive temperature.
Typical ratings:
No-overload use
P
cont.max
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I
2hd
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most IEC 60034 motors at the nominal
voltage, 230 V, 400 V, 500 V or 690 V.
ACS800-
04 size
Nominal
ratings
No-
over-
load
use
Light-
overload use
Heavy-duty
use
Size Air
flow
Heat dis-
sipa-
tion
(5
I
cont.m
ax
A
I
max
A
P
cont.max
kW
I
2N
A
P
N
kW
I
2hd
A
P
hd
kW
m
3
/h
W