Installation checklist 83
8
Installation checklist
What this chapter contains
This chapter contains the installation checklist.
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person. Read the
Safety
instructions
(page 11) in this manual before you do work on the unit.
Check
MECHANICAL INSTALLATION
The ambient operating conditions are allowed.
See
Ambient conditions
(page 122),
IEC data
(page 99) or
NEMA data
(page 114).
The unit is fixed properly on floor and a vertical non-flammable wall.
See
Mechanical installation
(page 33).
The cooling air flows freely.
ELECTRICAL INSTALLATION
See
Planning the electrical installation
(page 37),
Electrical installation
(page 63).
The motor and the driven equipment are ready for start.
See
Motor selection and compatibility
(page 38),
Motor connection
(page 120).
The +E202 EMC filter capacitors are disconnected if the drive is connected to an IT
(ungrounded) system.
The capacitors are reformed if stored over one year (refer to
Capacitor reforming instructions
(3BFE64059629 [English]).