106 Technical data
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0170-5 191 3820 250 550 000 500 ABB Control OFAF1H250 1
-0210-5 243 4510 315 1 100 000 500 ABB Control OFAF2H315 2
-0260-5 291 4510 315 1 100 000 500 ABB Control OFAF2H315 2
-0320-5 424 8280 500 2 900 000 500 ABB Control OFAF3H500 3
-0400-5 498 10200 630 4 000 000 500 ABB Control OFAF3H630 3
-0440-5 543 10200 630 4 000 000 500 ABB Control OFAF3H630 3
-0490-5 590 10200 630 4 000 000 500 ABB Control OFAF3H630 3
-0550-5 669 13500 800 7 400 000 500 ABB Control OFAF3H800 3
-0610-5 702 13500 800 7 400 000 500 ABB Control OFAF3H800 3
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0140-7 126 2400 160 220 000 690 ABB Control OFAA1GG160 1
-0170-7 156 2850 200 350 000 690 ABB Control OFAA1GG200 1
-0210-7 191 3820 250 700 000 690 ABB Control OFAA2GG250 2
-0260-7 217 3820 250 700 000 690 ABB Control OFAA2GG250 2
-0320-7 298 4510 315 820 000 690 ABB Control OFAA2GG315 2
-0400-7 333 6180 400 1 300 000 690 ABB Control OFAA3GG400 3
-0440-7 377 8280 500 3 800 000 690 ABB Control OFAA3H500 3
-0490-7 423 8280 500 3 800 000 690 ABB Control OFAA3H500 3
-0550-7 468 8280 500 3 800 000 690 ABB Control OFAA3H500 3
-0610-7 533 10800 630 10 000
000
690 Bussmann 630NH3G-690
**
3
** rated breaking capacity only up to 50 kA
1)
minimum short-circuit current of the installation
Note 1: See
Thermal overload and short-circuit protection
(page 46). For UL recognized fuses, see
NEMA data
(page 114).
Note 2: In multi-cable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
00096931, 00556489
gG fuses
ACS800-
04 size
Input
current
Min.
short-
circuit
current
1)
Fuse
AAA
A
2
s
V Manufacturer Type IEC
size