110   Technical data
Note 1: The supply transformer minimum power in kVA is calculated with a z
k
 value of 6% and frequency 
50 Hz. 
Note 2: The table is not intended for transformer selection - that must be done separately.
The following parameters can effect on the correct operation of the protection:
• cable length: The longer the cable the weaker the fuse protection, as the long cable limits the fault 
current.
• cable size: The smaller the cable cross-section the weaker the fuse protection, as the small cable 
size limits the fault current.
• transformer size: The smaller the transformer the weaker the fuse protection, as the small 
transformer limits the fault current.
• transformer impedance: The higher the 
z
k
 the weaker the fuse protection as high impedance limits 
the fault current.
-0320-5 2 × (3×120) 
Cu
3 × (3×95) Al 530 570 670 370 370 370
-0400-5 2 × (3×150) 
Cu
2 × (3×240) 
Al
660 720 840 440 440 480
-0440-5 3 × (3×95) Cu 3 × (3×150) 
Al
660 720 840 500 570 760
-0490-5 3 × (3×120) 
Cu
3 × (3×185) 
Al
660 720 840 520 570 760
-0550-5 2 × (3×240) 
Cu
3 × (3×240) 
Al
880 980 1200 580 670 880
-0610-5 3 × (3×150) 
Cu
3 × (3×240) 
Al
880 980 1200 610 670 880
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0140-7 3×70 Cu 3×95 Al 220 220 240 160 160 160
-0170-7 3×95 Cu 3×120 Al 260 260 280 190 190 190
-0210-7 3×120 Cu 3×150 Al 340 360 390 230 230 230
-0260-7 3×150 Cu 3×185 Al 340 360 390 260 260 260
-0320-7 3×240 Cu 2 × (3×120) 
Al
400410430360360360
-0400-7 3×240 Cu 3 x (3×70) Al 550 570 610 400 400 400
-0440-7 2 × (3×120) 
Cu
2 × (3×150) 
Al
730 780 860 460 460 460
-0490-7 2 × (3×120) 
Cu
3 × (3×95) Al 730 780 860 510 510 510
-0550-7 2 × (3×150) 
Cu
3 × (3×120) 
Al
730 780 860 560 560 560
-0610-7 3 × (3×95) Cu 3 × (3×150) 
Al
960 1000 1100 640 640 640
PDM code: 00556489 A
ACS800-04 
size
Cable type Supply transformer minimum apparent power 
S
N
 (kVA)
Copper Aluminum Maximum cable length with gG 
fuses
Maximum cable length with aR 
fuses
10 m 50 m 100 m 10 m 100 m 200 m