Technical data 117
-0320-7 273 500 600 Bussmann JJS-500 T
-0400-7 325 500 600 Bussmann JJS-500 T
-0440-7 370 500 600 Bussmann JJS-500 T
-0490-7 407 600 600 Bussmann JJS-600 T
-0550-7 463 600 600 Bussmann JJS-600 T
-0610-7 513 700 600 Ferraz A4BY700 L
Note 1: See
Thermal overload and short-circuit protection
(page 46).
Note 2: In multi-cable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve
of the fuse does not exceed the melting curve of the fuse mentioned in the table.
00096931
ACS800-U4
type
Input
current
Fuse
A A V Manufacturer Type UL class