Technical data
100
Cable types
Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Cable Entries
Brake resistor, input and motor cable (per phase) terminal sizes, accepted cable
diameters and tightening torques are given below
.
* with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf ft
Dimensions and weights
Copper cables with concentric copper shield
Max. load
current
A
Cable type
AWG/kcmil
31 10
44 8
57 6
75 4
88 3
101 2
114 1
132 1/0
154 2/0
176 3/0
202 4/0
224 250 MCM or 2 x 1
251 300 MCM or 2 x 1/0
273 350 MCM or 2 x 2/0
PDM code: 00096931-C
Frame size U1, V1, W1, U2, V2, W2, UDC+, UDC- Grounding PE
Wire size Wire Ø
(UL type 1)
Tightening
torque
Wire size Tightening
torque
AWG in. lbf ft AWG lbf ft
R5 4...2/0 1.39 11.1 4...2/0 11.1
R6 3/0 ... 350 MCM * 2.09 14.8...29.5 4/0 5.9
Frame size UL type 1
Height Width Depth Weight
in. in. in. lb
R5 32.03 10.43 15.35 143
R6 38.19 11.81 17.28 220