Technical data
101
UL/CSA markings
C-UL US listing and CSA marking are pending for the ACS800-U11 and ACS800-11 units of UL type 1.
UL
The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical
amperes at the drive nominal voltage (600 V maximum for 690 V units) when protected by T class
fuses.
The drive provides overload protection in accordance with the National Electrical Code (US). See
ACS800 Firmware Manual for setting. Default setting is off, must be activated at start-up.
The drives are to be used in a heated indoor controlled environment. See section Ambient conditions
for specific limits.