Technical data
90
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and
IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Cable entries
Mains, DC link and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below
.
* with cable lugs 16...70 mm
2
, tightening torque 20...40 Nm
Dimensions, weights and noise
Copper cables with concentric
copper shield
Aluminium cables with concentric
copper shield
Max. load
current
A
Cable type
mm
2
Max. load
current
A
Cable type
mm
2
34 3x6 61 3x25
47 3x10 75 3x35
62 3x16 91 3x50
79 3x25 117 3x70
98 3x35 143 3x95
119 3x50 165 3x120
153 3x70 191 3x150
186 3x95
215 3x120
249 3x150
284 3x185
PDM code: 00096931-C
Frame size U1, V1, W1, U2, V2, W2, UDC+,UDC- Earthing PE
Wire size Max. cable Ø
IP 21
Tightening
torque
Wire size Tightening
torque
mm
2
mm Nm mm
2
Nm
R5 16…70 35 10 16…70 15
R6 95...185 * 53 20…40 95 8
Frame size IP 21 Noise
Height Width Depth Weight
mm mm mm kg dB
R5 816 265 390 65 70
R6 970 300 439 100 73