Planning the electrical installation
46
Selecting the power cables 
General rules
Dimension the mains (input power) and motor cables according to local 
regulations:
• The cable must be able to carry the drive load current. See chapter Technical 
data for the rated currents.
• The cable must be rated for at least 70 
°C maximum permissible temperature of 
conductor in continuous use. For US, see Additional US requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must 
be rated according to permissible touch voltage appearing under fault conditions 
(so that the fault point voltage will not rise excessively when a ground fault 
occurs).
• 600 VAC cable is accepted for up to 500 VAC. 750 VAC cable is accepted for up 
to 600 VAC. For 690 VAC rated equipment, the rated voltage between the 
conductors of the cable should be at least 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 HP), 
symmetrical shielded motor cable must be used (figure below). A four-conductor 
system can be used up to frame size R4 with up to 30 kW (40 HP) motors, but 
shielded symmetrical motor cable is recommended.  
A four-conductor system is allowed for input cabling, but shielded symmetrical cable 
is recommended. To operate as a protective conductor, the shield conductivity must 
be as follows when the protective conductor is made of the same metal as the phase 
conductors: 
Compared to a four-conductor system, the use of symmetrical shielded cable 
reduces electromagnetic emission of the whole drive system as well as motor 
bearing currents and wear. 
The motor cable and its PE pigtail (twisted shield) should be kept as short as 
possible in order to reduce electromagnetic emission.
Cross-sectional area of the phase 
conductors 
S (mm
2
) 
Minimum cross-sectional area of the 
corresponding protective conductor
S
p
 (mm
2
) 
S < 16 S
16 < S <
 35 16
35 < S S/2