292 Parameters
33.61 Value counter 2
warn limit
Sets the limit for value counter 2.
With a positive limit, bit 5 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
0
-2147483008 …
2147483008
Limit for value counter 2. -
33.62 Value counter 2
function
Configures value counter 2. 0000b
0000b…0011b Value counter 2 configuration word. 1 = 1
33.63 Value counter 2
source
Selects the signal to be monitored by value counter 2. Not selected
Not selected None (counter disabled). 0
Motor speed 01.01 Motor speed used (see page 117). 1
Other Source selection (see Terms and abbreviations on page 114). -
33.64 Value counter 2
divider
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
1.000
0.001 …
2147483.000
Divisor for value counter 2. -
33.65 Value counter 2
warn message
Selects the optional warning message for value counter 2. Value
counter 2
exceeded
Value counter 2
exceeded
A88B Value counter 2. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
5
Maintain motor
bearing
A880 Motor bearing.10
No. Name/Value Description Def/FbEq16
Bit Function
0 Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of 33.01) switches to 1,
and remains so until 33.60 is reset. The warning (if enabled) also stays active until 33.60
is reset.
1 Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.65) is given when the limit is reached
2…15 Reserved