Capa-
citance
Heavy-duty use
Light-overload
use
No-overload use
Frame
ACS880-
204-…
CP
Hd
I
Hd
P
Ld
I
Ld
S
N
P
N
I
max
I
N
I
N
mF
kW
(DC)
A (DC)
kW
(DC)
A (DC)kVAkWA (DC)A (AC)A (DC)
27.001386142017791823187218532848156618993×R8i1570A-7
36.001832187723512409247424493765207025104×R8i2070A-7
54.002724279234963583367936425598307837326×R8i3080A-7
■ Definitions
Nominal ratings
supply voltage range (see the technical data)
U
N
nominal output current (available continuously with no over-loading)
I
N
maximum output current. Available for 10 s at start, otherwise as long as allowed by module tem-
perature.
I
max
nominal output power
P
N
nominal apparent power
S
N
Light-overload use (10% overload capability) ratings
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
I
Ld
output power in light-overload use
P
Ld
Heavy-duty use (50% overload capability) ratings
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
I
Hd
output power in heavy-duty use
P
Hd
Capacitance
Nominal DC link capacitanceC
Note:
The ratings apply to units without option +C132 (marine type approval). For ratings of units
with option +C132, see ACS880 +C132 marine type-approved drive modules and module
packages supplement (3AXD50000037752 [English]).
For input frequency f
1
, see Electrical power network specification (page 291).
Note:
The ratings apply at an ambient temperature of 40 °C (104 °F).