Default I/O diagram of the supply control unit
The diagram below shows the default I/O connections on the supply control unit (A51), and
describes the use of the connections in the supply unit. Under normal circumstances, the
factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
DescriptionTerminal
Drive-to-drive linkXD2D
Not in use by default
B1
A2
BGND3
Shield4
Drive-to-drive link termination switch
1)
D2D.TERM
RS485 connectionX485
Cooling fan monitoring (CIO module)
B5
A6
BGND7
Shield8
Relay outputsXRO1, XRO2, XRO3
XRO1: Running
2)
(Energized = running)
250 V AC / 30 V DC, 2 A
Norm. closedNC11
CommonCOM12
Norm. openNO13
XRO2: Fault (-1)
2)
(Energized = no fault)
250 V AC / 30 V DC, 2 A
Note: If drive is equipped with a liquid cool-
ing unit, the relay output controls the cooling
unit start signal. Then the selection Fault(-
1) may also be changed to Started by bit
12 of parameter 195.12. See ACS880 diode
supply control program firmware manual
(3AUA0000103295 [English]).
Norm. closedNC21
CommonCOM22
Norm. openNO23
XRO3: MCB ctrl
3)
(Energized = closes
main contactor/breaker) 250 V AC /
30 V DC, 2 A
Norm. closedNC31
CommonCOM32
Norm. openNO33
Safe torque off
4)
XSTO, XSTO OUT
XSTO: Factory connection. Both circuits must be closed for the drive to start
(IN1 and IN2 must be connected to OUT).
OUT1
SGND2
IN13
IN24
XSTO OUT: Not in use.
IN15
SGND6
IN27
SGND8
Digital inputsXDI
50 The control unit