Control unit
Replacing the memory unit
After replacing a control unit, you can keep the existing parameter settings by transferring
the memory unit from the defective control unit to the new control unit.
WARNING!
Do not remove or insert the memory unit when the control unit is powered.
1.
Stop the drive and do the steps in section Electrical safety precautions (page 36) before
you start the work.
2. Make sure that the control unit is not powered.
3. Remove the fastening screw and pull the memory unit out.
4. Install a memory unit in reverse order.
Replacing the BCU control unit battery
Replace the real-time clock battery if the BATT OK LED is not illuminated when the control
unit is powered.
1.
Stop the drive and do the steps in section Electrical safety precautions (page 36) before
you start the work.
2. Undo the fastening screw and remove the battery.
3. Replace the battery with a new BR2032 battery.