134 Technical data
Ratings
Definitions
Derating
Ambient temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor (k):
Module type
ACS880-304LC...
No overload use Light overload
use
Heavy-duty
use
I
1
I
2
I
max
S
n
I
max
P
n
I
Ld
P
Ld
I
Hd
P
Hd
A (AC) A (DC) A (DC) kVA A (AC) kW (DC) A (DC) kW
(DC)
A (DC) kW
(DC)
U
N
= 690 V
-0820A-7+A019 820 1000 1400 980 1143 932 960 895 800 745
-1540A-7+A019 1540 1880 2632 1840 2149 1752 1805 1682 1504 1401
-2290A-7+A019 2290 2805 3927 2737 3206 2614 2693 2509 2244 2091
-3040A-7+A019 3040 3720 5208 3633 4252 3466 3571 3328 2976 2773
3AXD00000601909.XLS
Nominal ratings
U
N
Nominal input voltage. For U
1
, see Electrical power network specification on page 139. For U
2
, see
DC connection data on page 139.
I
1
Continuous rms input (AC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
2
Continuous rms output (DC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
max
Maximum output (DC) current. Available for 10 s at start, otherwise as long as allowed by module
temperature.
S
n
Nominal apparent (AC) power
I
max
Maximum input (AC) current
P
n
Nominal output (DC) power
Light-overload use (50% overload capability) ratings
I
Ld
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Ld
Output power in light-overload use
Heavy-duty use (50% overload capability) ratings
I
Hd
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Hd
Output power in heavy-duty use
T
1.00
0.95
+45 °C
+113 °F
+55 °C
+131 °F
k
0.90
A
CS880-304LC ACS880-104LC_ambient temp derating curve.pd
f
Coolant temperature derating
See section Temperature limits (page 84).
Antifreeze content derating
See section Temperature limits (page 84).
Altitude derating
At altitudes 1000 2000 m (3281 6562 ft) above sea level, the output current derating
is 1 percentage point for every added 100 m (328 ft). For example, the derating factor for
1500 m (4921 ft) is 0.95. For altitudes above 2000 m (6562 ft), contact ABB.
For a more accurate derating, use the DriveSize PC tool.
Type equivalence table
FrameBasic module typeSupply unit type
U
N
= 690 V
6-pulse
D8TACS880-304LC-0490A-7+A018ACS880-307LC-0490A-7+A018
D8TACS880-304LC-0780A-7+A018ACS880-307LC-0780A-7+A018
D8TACS880-304LC-1060A-7+A018ACS880-307LC-1060A-7+A018
2×D8TACS880-304LC-0780A-7+A018ACS880-307LC-1470A-7+A018
2×D8TACS880-304LC-1060A-7+A018ACS880-307LC-2000A-7+A018
3×D8TACS880-304LC-1060A-7+A018ACS880-307LC-3000A-7+A018
4×D8TACS880-304LC-1060A-7+A018ACS880-307LC-4000A-7+A018
5×D8TACS880-304LC-1060A-7+A018ACS880-307LC-5000A-7+A018
6×D8TACS880-304LC-1060A-7+A018ACS880-307LC-6000A-7+A018
12-pulse
2×D8TACS880-304LC-0490A-7+A018ACS880-307LC-0920A-7+A004+A018
2×D8TACS880-304LC-0780A-7+A018ACS880-307LC-1470A-7+A004+A018
2×D8TACS880-304LC-1060A-7+A018ACS880-307LC-2000A-7+A004+A018
4×D8TACS880-304LC-0780A-7+A018ACS880-307LC-2940A-7+A004+A018
4×D8TACS880-304LC-1060A-7+A018ACS880-307LC-4000A-7+A004+A018
6×D8TACS880-304LC-1060A-7+A018ACS880-307LC-6000A-7+A004+A018
Technical data 91