EasyManua.ls Logo

ABB ACS880-307LC - Internal Cooling Circuit; Contents of this Chapter; Applicability; Internal Cooling System

ABB ACS880-307LC
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal cooling circuit
Contents of this chapter
The cooling system of a liquid-cooled drive consists of two circuits: the internal cooling circuit
and the external cooling circuit. The internal cooling circuit covers the heat-generating
electrical components of the drive and transfers the heat to the cooling unit. In the cooling
unit, the heat is transferred to the external cooling circuit which is usually part of a larger
external cooling system. This chapter deals with the internal cooling circuit.
Applicability
The information in this chapter is applicable to cabinet-built ACS880 liquid-cooled drives.
Except where otherwise indicated, the information is also applicable to drives built out of
ACS880 liquid-cooled multidrive modules.
Internal cooling system
Each cubicle has an inlet and an outlet manifold, fitted with a stop valve and a drain valve.
The stop valves can be closed to isolate all modules in the cubicle from the main cooling
circuit.
In cabinet line-ups built by ABB, valves are color-coded:
Blue Open during operation
Red Closed during operation
The following diagram shows the coolant pipe connections in a drive system consisting of
a supply unit and an inverter unit.
8
Internal cooling circuit 79

Table of Contents

Related product manuals