Cooling data and noise
Noise level
Pressure
loss
Coolant flow rateCoolant volume
Supply unit type
ACS880-307LC-…
AverageModules +
cabinet
ModulesModules +
cabinet
Modules
dB (A)kPal/minl/minll
U
N
= 690 V
6-pulse
6512020143.50.60490A-7+A018
6512020143.50.60780A-7+A018
6512020143.50.61060A-7+A018
6512034284.21.21470A-7+A018
6512034284.21.22000A-7+A018
6712054427.71.83000A-7+A018
6712068568.42.44000A-7+A018
68120887011.93.05000A-7+A018
681201028412.63.66000A-7+A018
12-pulse
6712034284.21.20920A-7+A004+A018
6712034284.21.21470A-7+A004+A018
6712034284.21.22000A-7+A004+A018
6812068568.42.42940A-7+A004+A018
6812068568.42.44000A-7+A004+A018
681201028412.63.66000A-7+A004+A018
Terminal and cable entry data for the input power cable
These drawings (from front, side and above) show the terminal and cable entry dimensions
for incoming cubicles. The dimensions are given in millimeters. Tightening torque for the
cable lug connection depends on the bolt size and type. See section Tightening
torques (page 98).