The product family Advant Controller 500 control system is designed according to EN 61131-2 IEC
61131-2 standards. Data, different from IEC 61131, are caused by the higher requirements of Maritime
Services.
System data
Operating and ambient conditions
Voltages, according to EN 61131-2
process and supply
voltage
24 V DC (-15 %, +20 % without ripple)
absolute limits 19.2 V...30 V inclusive ripple (see remarks above)
ripple < 5 %
24 V DC
protection against
reverse polarity
10 s
line voltage 120 V AC (-15 %, +10 %) 120 V AC
frequency 47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
line voltage 230 V AC (-15 %, +10 %) 230 V AC
frequency 47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
wide-range supply
line voltage 102 V...264 V / 120 V...240 V (-15 %, +10 %)
120-240 V AC
frequency 47 Hz..62.4 Hz / 50...60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply interruption < 10 ms,
time between 2 interruptions > 1 s, PS2
AC supply Interruption < 0.5 periods,
time between 2 interruptions > 1 s
Important: Exceeding the maximum power supply voltage (>30 V DC) for process or supply
voltages could lead to unrecoverable damage of the system. The system could be destroyed.
Temperature
operating 0 °C...+60 °C (horizontal mounting of modules)
0 °C...+40 °C (vertical mounting of modules and output
load reduced to 50 % per group)
storage -25 °C...+75 °C
transport -25 °C...+75 °C
Temperature of the Lithium battery
operating 0 °C...+60 °C
storage -20 °C...+60 °C
transport -20 °C...+60 °C
Humidity
max. 95 %, without condensation
Air pressure
operating > 800 hPa / < 2000 m
storage > 660 hPa / < 3500 m