V2 AC500 Hardware 1-5 System data AC500 / Issued: 05.2007
Creepage distances and clearances
The creepage distances and clearances meet the overvoltage category II, pollution degree 2.
Insulation test voltages, routine test, according to EN 61131-2
230 V circuits against other circuitry 2500 V surge 1.2/50 µs
120 V circuits against other circuitry 1500 V surge 1.2/50 µs
120 V to 240 V circuits against other circuitry 2500 V surge 1.2/50 µs
24 V circuits (supply, 24 V inputs/outputs), if they are
electrically isolated against other circuitry
500 V surge 1.2/50 µs
COM interfaces, electrically isolated 500 V surge 1.2/50 µs
FBP interface 500 V surge 1.2/50 µs
Ethernet 500 V surge 1.2/50 µs
ARCNET 500 V surge 1.2/50 µs
230 V circuits against other circuitry 1350 V AC 2 s
120 V circuits against other circuitry 820 V AC 2 s
120 V to 240 V circuits against other circuitry 1350 V AC 2 s
24 V circuits (supply, 24 V inputs/outputs), if they are
electrically isolated against other circuitry
350 V AC 2 s
COM interfaces, electrically isolated 350 V AC 2 s
FBP interface 350 V AC 2 s
Ethernet 350 V AC 2 s
ARCNET 350 V AC 2 s
Power supply units
For the supply of the modules, power supply units according to PELV specifications must be used.