AquaMaster 3
Electromagnetic flowmeter 5 Specification
44 User Guide OI/FET2XX–EN Rev. E
Telemetry applications (option)
GSM / SMS Modem
Mounting:
Internal
Frequency bands:
Quad band: 850 / 900 / 1800 / 1900 MHz
Functions:
SMS auto report of flow and optionally pressure
logger data (typically 1 s or 1 min. average)
SMS report frequency: typically daily
SMS alarm reporting at time of event, for example
power loss, limited to 1 per day
SMS configuration of flowmeter
SMS diagnosis of flowmeter
SMS total / tariff auto report
GSM Antenna (option)
Quad band operation:
850 / 900 / 1800 / 1900 M Hz
Mounting:
Integral with transmitter or remote.
Antenna environmental:
IP66 (NEMA4) waterproof for accidental submersion
Note. The GSM does not operate with integral
antenna under water.
General advice is to mount the antenna as high as
possible, always outside of any metal enclosure and
not under the surface of the ground.
Pressure system – external transducer
(option)
Pressure range
16 bar Abs.
Connection
Standard quick-fit male probe connector via an adapter
cable
Operating temperature range
–20 (ambient) to 70 °C (–4 to 158 °F)
Protect the sample and transducer from freezing.
Accuracy (typical)
±0.4 % of range
Thermal error band (typically 100 °C [212 °F])
±1.5 % span
Cable length
5 or 10 m (16 or 33 ft.)
Temperature ranges
Operation outside ambient temperature limits of 0 to
45 °C (32 to 113 °F) reduces battery capacity and
shortens battery life.
Response time (programmable)
Minimum
1 s (mains-powered)
15 s (battery-powered + external renewable energy)
Device languages
English
French
German
Spanish
Italian
Dutch