7 ADDRESSABLE PARAMETERS
7.1 COMMANDER 100/V100 – Coils
Coil No. Variable Label Read/Write Limits/Values
01 Process Variable Fail State R 1 = Failed
02 Remote Set Point Fail State R 1 = Failed
03 A/D Converter Fail State R 1 = Failed
06 Alarm State 1 R 1 = Active
07 Alarm Indicator 1 R 1 = On
08 Alarm State 2 R 1 = Active
09 Alarm Indicator 2 R 1 = On
14 Digital Input State R 1 = On
15 Digital Output State R 1 = On
16 Relay 1 State R 1 = On
17 Relay 2 State R 1 = On
19 On/Off Output 1 (Heat) R 1 = On
20 On/Off Output 2 (Cool) R 1 = On
30 Auto/Manual State RW 0 = Auto; 1 = Manual
31 Control Action W 0 = Reverse; 1 = Direct
32 Select Local Set Point W 1 = Local
33 Select Remote Set Point W 1 = Remote
34 Select Fixed Set Point 1 W 1 = Selected
35 Select Fixed Set Point 2 W 1 = Selected
36 Select Fixed Set Point 3 W 1 = Selected
37 Select Fixed Set Point 4 W 1 = Selected
7.2 COMMANDER 100/V100 – Registers
7.2.1 Analog Inputs
Register Variable Label Read/Write Limits/Values
2 Process Variable Input R –999 to 9999
3 PV Decimal Places R 0 to 4
5 Remote Set Point Input R –999 to 9999
6 Remote SP Decimal Places R 0 to 2