7 ADDRESSABLE PARAMETERS…
…7.2 COMMANDER 100/V100 – Registers
7.2.2 Control Settings
Register Variable Label Read/Write Limits/Values
12 Process Variable Input R –999 to 9999
13 Control Set Point R –999 to 9999
14 Output 1 RW* –80 to 1100
15 Auto/Manual State RW 0 = Auto; 1 = Manual
0 = Local
1 = Remote
2 = Fixed Set Point 1
16 Set Point Select RW 3 = Fixed Set Point 2
4 = Fixed Set Point 3
5 = Fixed Set Point 4
6 = Ramp/Soak
17 Output 2 RW* –80 to 1100
18 Fixed Set Point 1 RW –999 to 9999
19 Fixed Set Point 2 RW –999 to 9999
20 Fixed Set Point 3 RW –999 to 9999
21 Fixed Set Point 4 RW –999 to 9999
22** Valve Deadband RW 1 to 9999
23** Valve Travel Time RW 1 to 5000 sec
24** Valve Drive RW* 0 = Close
1 = Stop
2 = Open
25 Proportional Band 1 RW 1 to 9999
26 Integral Action Time RW 0 to 7200
27 Derivative Action Time RW 0 to 9999
28 Manual Reset RW 0 to 1000
29 Cycle Time 1 RW 9 to 3000
30 Cycle Time 2 RW 9 to 3000
31 Proportional Band 2 RW 1 to 9999
32 Overlap RW 100 to –100
33 Control Mode 1 (Heat) R 0 = On/Off
34 Control Mode 2 (Cool) R 1 = Analog Control***
2 = Time Proportioning
35 Control Output 1 Action RW 0 = Reverse; 1 = Direct
36 Auto/Manual State RW 0 = Auto; 1 = Manual
* These registers can only be written to when the controller is in Manual Mode.
Control outputs 1 and 2 are only applicable to C100 instruments.
** V100 Instruments only
*** Control Mode 1 only