ABB C100 - 7 ADDRESSABLE PARAMETERS; 7.2 COMMANDER 100;V100 - Registers; 7.2.2 Control Settings

ABB C100
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
7 ADDRESSABLE PARAMETERS…
…7.2 COMMANDER 100/V100 – Registers
7.2.2 Control Settings
Register Variable Label Read/Write Limits/Values
12 Process Variable Input R –999 to 9999
13 Control Set Point R –999 to 9999
14 Output 1 RW* –80 to 1100
15 Auto/Manual State RW 0 = Auto; 1 = Manual
0 = Local
1 = Remote
2 = Fixed Set Point 1
16 Set Point Select RW 3 = Fixed Set Point 2
4 = Fixed Set Point 3
5 = Fixed Set Point 4
6 = Ramp/Soak
17 Output 2 RW* –80 to 1100
18 Fixed Set Point 1 RW –999 to 9999
19 Fixed Set Point 2 RW –999 to 9999
20 Fixed Set Point 3 RW –999 to 9999
21 Fixed Set Point 4 RW –999 to 9999
22** Valve Deadband RW 1 to 9999
23** Valve Travel Time RW 1 to 5000 sec
24** Valve Drive RW* 0 = Close
1 = Stop
2 = Open
25 Proportional Band 1 RW 1 to 9999
26 Integral Action Time RW 0 to 7200
27 Derivative Action Time RW 0 to 9999
28 Manual Reset RW 0 to 1000
29 Cycle Time 1 RW 9 to 3000
30 Cycle Time 2 RW 9 to 3000
31 Proportional Band 2 RW 1 to 9999
32 Overlap RW 100 to –100
33 Control Mode 1 (Heat) R 0 = On/Off
34 Control Mode 2 (Cool) R 1 = Analog Control***
2 = Time Proportioning
35 Control Output 1 Action RW 0 = Reverse; 1 = Direct
36 Auto/Manual State RW 0 = Auto; 1 = Manual
* These registers can only be written to when the controller is in Manual Mode.
Control outputs 1 and 2 are only applicable to C100 instruments.
** V100 Instruments only
*** Control Mode 1 only