7 ADDRESSABLE PARAMETERS…
7.3 COMMANDER 150/160 – Coils
Coil No. Variable Label Read/Write Limits/Values
1 Process Variable Fail State R 1 = Failed
3 A/D Converter Fail State R 1 = Failed
6 Alarm State 1 R 1 = Active
7 Alarm Indicator 1 R 1 = On
8 Alarm State 2 R 1 = Active
9 Alarm Indicator 2 R 1 = On
10 Alarm State 3 R 1 = Active
11 Alarm Indicator 3 R 1 = On
14 Digital Input State R 1 = On
15 Digital Output State R 1 = On
16 Relay 1 State R 1 = On
17 Relay 2 State R 1 = On
21 Global Maths Reset W 1 = Reset
22 Maximum Values Reset W 1 = Reset
23 Minimum Values Reset W 1 = Reset
24 Average Values Reset W 1 = Reset
7.4 COMMANDER 150/160 – Registers
7.4.1 Analog Inputs
Register Variable Label Read/Write Limits/Values
1 + 2 Process Variable Input R –9999 to 99999
3 PV Decimal Places R 0 to 4
7.4.2 Alarm Settings
Register Variable Label Read/Write Limits/Values
50 + 51 Alarm Trip 1 RW –9999 to 99999
52 + 53 Alarm Trip 2 RW –9999 to 99999
54 + 55 Alarm Trip 3 RW –9999 to 99999
56 Alarm Hysteresis Value RW 0 to 100
0 = None
57 Alarm Type 1 R 1 = High Process
58 Alarm Type 2 R 2 = Low Process
59 Alarm Type 3 R 3 = High Latch
4 = Low Latch