EasyManua.ls Logo

ABB COMMANDER 300 - Multiple Read Parameters

ABB COMMANDER 300
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
…8 COMMUNICATION
8.6.3 Heat/Cool Parameters
Parameter Mnemonic
Command
Reply Interpretation
Read
(R)
Write
(W)
Control Page Parameters (Heat/Cool)
Cycle Time (Cool)
CC Yes Yes
1.0 to 300.0
Proportional Band (Cool)
L2 Yes Yes
0.1 to 999.9
Integral Action Time (Cool)
L3 Yes Yes
1 to 7200 (7201 = OFF)
Manual Reset (Cool)
L4 Yes Yes
0.0 to 99.9
Crossover Output Value
Q1 Yes Yes
0.0. to 100.0
Transition Bandwidth
Q2 Yes Yes
0.0 to 100.0
Output Off Hysteresis
Q3 Yes Yes
0.0 to 25.0
Heat Output High Limit
Q4 Yes Yes
0.0. to 100.0
Cool Output High/Low Limit
Y1 Yes Yes
0.0. to 100.0
Heat Output
Y2 Yes No
0.0 to 100.0
Cool Output
Y3 Yes No
0.0 to 100.0