8 COMMUNICATION…
8.4 Communication Examples
The following examples show typical master-to-slave transmissions and the subsequent slave-
to-master replies. For Error Code and Parameter interpretations refer to Sections 8.5 and 8.6.
MSTX 05
End of text
c)
Command STX M05 MG EETX
Command understood
Controller number 5
Reply:
MG ETX
Controller number five
'Multiple Read' command
Start of text
05 MV 60.0 ACK
05 IS 0
05 SP 65.0 ACK
05 OP 72.5 ACK
ACK
Measured value 60.0
Instrument status 0 *
Control setpoint 65.0
Control output 72.5%
ETB
ETB
ETB
ETB ACK
Multiple read mnemonic
End of transmission block
* '0' is the normal status see Fig. 8.7
overleaf.
MSTX 05
End of text
d)
Command STX M05MV ETX
05 19
Command not understood
Error code 19
Reply 0519 NNAK
MV ETX
Measured (process) Variable
Controller number five
'Multiple Read' command
Start of text
NAK
Controller number five
i.e. the 'Multiple Read' command canno
t
be used for a single parameter se
e
Section 8.6.
06
RSTX 06
End of text
a)
PB 100.0
Command understood
Proportional band is 100%
PB ETX
Proportional band
Controller number six
'Read' command
Start of text
ACK
Controller number 06
Command STX R06PB EETX
Reply 06PB100.0 ACK
07
RSTX 07
End of text
b)
02 NAK
Command not understood
Error code 2
IX ETX
Parameter 'IX'
Controller number seven
'Read' command
Start of text
Controller number seven
i.e. 'IX' in the original command is not a
recognised 'Read' parameter se
e
Section 8.6.
Command STX R07IX EETX
Reply 0702 NAK