Loading...
10
…8 COMMUNICATION
…8.4 Communication Examples
11
WSTX 11
End of text
e)
Command STX W11A170 EETX
A1 70
Command understood
Alarm A setting is 70
Reply 11LA70 ACK
LA 70 ETX
Write to 70
Alarm A trip point
Controller number eleven
'Write' command
Start of text
ACK
Controller number eleven
05
WSTX 05
End of text
f)
Command STX W05L21 EETX
03
Command not understood
Error code 3
Reply 0503 NNAK
L2 1 ETX
Relay 2
energised
Relay 2 state
Controller number five
'Write' command
Start of text
NAK
Controller number five
i.e. 'L2' in the original command is not
a recognised 'Write' parameter. Th
e
'L2' mnemonic can only be used with
the 'Read' command.
Self-tune state
(0 = off, 1 = on)
Auto/Manual state
(0 = auto, 1 = manual)
Set Point type
(0 = local, 1 = second)
Security level 1 access
(0 = no access, 1 = access)
Security level 2 access
(0 = no access, 1 = access)
Power failure status
(0 = no power failure, 1 = power failure)
Process variable failure
(0 = no failure, 1 = failure)
Remote set point failure
(0 = no failure, 1 = failure)
Position feedback failure
(0 = no failure, 1 = failure)
11 10 9 8 7 6 5 4 3 2 1 0MSB LSB
Unacknowledged alarm
(0 = no alarms unacknowledged,
1 = alarms unacknowledged)
Alarm 2 relay state
(0 = relay off, 1 = relay on)
Alarm 1 relay state
(0 = relay off, 1 = relay on)
Fig. 8.7 Instrument Status