Chapter 10 - Service
VI A 10 - 18 DCS 500 / DCS 600 Service Manual
Firmware download
with Windows NT 4.0
Recommendation It is strongly recommended:
To use the ABB bus cable (DCA 0021499 R0001).
To disconnect the laptop from mains supply during download.
The drive has to be grounded.
To switch off all other drives beside the destined unit (distur-
bances possible).
to provide save download transmission
Preparation
• Switch off auxiliary supply voltage of SDCS-POW-1.
•
Disconnect and remove SDCS-AMC x board (only
DCS 600).
• Disconnect any other equipment from X33 and X34.
• Connect bus cable from NPCU-02 to X33 or X34 at DCS con-
verter.
• Connect the interface NPCU-02 to COM1 at the PC.
• Set Jumper S2 on SDCS-CON-x from position 7-8 or 3-4 to 5-6.
• Copy the files distributed from ABB (see Software configuration
)
into designated pathes e.g.
C:\...\DCSx00
• Start HyperTerminal by double-click on CON2 download.ht.
This setup file configures HyperTerminal to communicate with the
SDCS-CON-x board.
3ADW000093R0701_DCS500B/DCS600_Service manual_e_g