Chapter 10 - Service
VI A 10 - 20 DCS 500 / DCS 600 Service Manual
Note:
Syntax error indicates EMI (Electromagnetic interference) in the in-
stallation.
check grounding
switch off all other electronic equipment
close and re-open HyperTerminal
Flash Erase
Type ls (+ Return).
Flash Program
Type rp (+ Return).
Terminal program shows a small rp
Open menu item TRANSFERS / SEND TEXT FILE… and select
the suitable firmware
Attention: Use DC21A2yy.rom with DCS 500B and
DC15A2yy.rom with DCS 600.
3ADW000093R0701_DCS500B/DCS600_Service manual_e_g