DCS500 Pin and Parameter list
A 87
MAIN_CONT_ON
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = command to put main contactor in off-state
-1 = command to put main contactor in on-state.
10910 FB_O: B SC: BO HL: - LL: - D: - U: -
TRIP_DC_BREAKER
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = no command to a dc breaker
-1 = command to open the dc breaker.
10911 FB_O: B SC: BO HL: - LL: - D: - U: -
DYN_BRAKE_ON
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = no command to a dynamic brake
-1 = command to close the dynamic brake.
10912 FB_O: B SC: BO HL: - LL: - D: - U: -
MOTOR_ACT
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = parameter set for motor 1 is active
-1 = parameter set for motor 2 is active.
10913 FB_O: B SC: BO HL: - LL: - D: - U: -
AUTO-RECLOSING
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = Auto-reclosing function is not active
-1 = Auto-reclosing function is active.
10914 FB_O: B SC: BO HL: - LL: - D: - U: -
COMM_FAULT
Signal of DRIVE LOGIC-function block ( S3/16 )
0 = there is no active communication fault in the drive
-1 = there is an active communication fault in the drive.
10915 FB_O: B SC: BO HL: - LL: - D: - U: -
RUN_DCF
Signal of DCF FIELDMODE-function block (S2/16 | S21.232)
Only active if DCF MODE = FEXLINK NODE1 or FEXLINK NODE2. Can be used to start
and stop a DCF 500B, if this converter is connected via FEX-LINK (X16: to X16:
connection) to a DCS 500B and no external start / stop command should be used to
control the field exciter. In this case connect this signal to input ON/OFF (901) and RUN1
(902) of the DRIVE LOGIC. The signal definition is:
0 = command to put DCF500B field exciter in off-state
-1 = command to put DCF500B field exciter in on-state
10916 FB_O: B SC: BO HL: - LL: - D: - U: -
RESET_DCF
Signal of DCF FIELDMODE-function block (S2/16 | S21.232)
Only active if DCF MODE = FEXLINK NODE1 or FEXLINK NODE2. Can be used to reset
faults at a DCF 500B, if this converter is connected via FEX-LINK (X16: to X16:
connection) to a DCS 500B and no external RESET command should be used to reset
faults at the field exciter. In this case connect this signal to input RESET (907) of the
DRIVE LOGIC. The signal definition is:
0 = no command to DCF500B field exciter
-1 = command to reset DCF500B field exciter faults
10917 FB_O: B SC: BO HL: - LL: - D: - U: -