EasyManua.ls Logo

ABB DCS 600 MultiDrive - Page 26

ABB DCS 600 MultiDrive
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 - Start-Up Instructions
IV F
2 - 14 DCS 600 Operating Instructions
Drive must not turn! Do not preset an external reference!
15.02 = 3
Activate the current controllers auto-tuning function.
Start the next two steps within the next 20 seconds!
Switch ON power.
DANGER: System components now energized!
Start drive.
When the display shows 0 (zero) stop drive; it may happen that the unit runs
armature-circuit current since EMF control is active.
If the unit aborts the auto-tuning routine with the signal 15.02 = -1, the probable
cause of this can be read out of Parameter 6.02 and has to be eliminated as far
as possible (supply, switching sequence etc.).
Afterwards repeat the auto-tuning routine.
If necessary, perform manual balancing.
Switch OFF power!
Read out values of:
41.11 = ......... 41.12 = ......... 43.02 = ......... 43.03 = ............ 43.06 = .........
Use values of 41.11 and 43.06 from the first auto-tuning routine.
Re-activate the field unit used by entering:
a) 15.05 = 1
or
b) 15.05 = 2
and install the supply fuses removed before!

Table of Contents

Other manuals for ABB DCS 600 MultiDrive

Related product manuals