Chapter 2 - Start-Up Instructions
IV F
2 - 34 DCS 600 Operating Instructions
DCS 600 and DCF 600 by FEXlink
Hardware
DCS 600 SDCS-AMC-DC or AMC-DC Classic board
DCF 601/ SDCS-AMC-DC or AMC-DC Classic board
DCF 602
Configuration For first field exciter
DCS 600 without SDCS-FEX-1 / SDCS-FEX-2
DCF 600 connection by FEXlink (X16)
Maincontactor of DCF 600 controlled by armature converter (FEXlink X16)
DCF 600 DI1 = H
⇒ connected to 48V
DI2 = H
⇒ connected to DCF 506
Associated publications
DCS 600 Technical Data 3ADW000054R0301 ABB Lampertheim
Software Description 3ADW000076R0401 ABB Lampertheim
Database GLOBAL\DEIND\DEIND051.NSF
Software settings
DCS 600 Parameter 41.03 = Rated field current
(only used for display)
DCF 601/ Parameter 15.16 = 5 operation mode
DCF 602
Parameter 15.21 = 1 Node = First field exciter
Parameter 15.22 = 2 FEXlink command
Parameter 46.07 = 3 FEXLINK
Parameter 43.13 = 4 or higher
Parameter 99.03 = Rated field current of
the motor
Note: Resetting of DCF 600 with FEXlink control (X16) is performed by switching OFF
(DISABLE reference) and ON (ENABLE reference) again:
Control Panel key
⇒ Control Panel key
(when in LOCAL mode) (when in LOCAL mode)