Chapter 2 - Start-Up Instructions
IV F
2 - 16 DCS 600 Operating Instructions
Start drive.
Increase reference value in LOCAL mode to 10 % of the maximum speed.
Drive should run up to 10 % of the rated voltage.
Use Potentiometer R2716 [on SDCS-CON-2 board] or R9 [on PS5311 board] to
set the tacho voltage to 10 % of the maximum tacho voltage.
Stop the drive and switch OFF power!
Only when an encoder (pulse encoder) is being used!
3.07 = Content of pulse counter *)
If the shape of the curve corresponds to the diagram below, this means
the wiring is correct and the pulses will be correctly evaluated [see
also documentation entitled Technical Data”, Chapter I/O boards].
*) This Parameter must be transmitted from the SDCS-CON-2 board to the SDCS-AMC-DC board!
Fig.: Curve shape of the encoders pulse counter for sense of rotation "forwards
Switch OFF power, thus stopping the drive; drive coasts.
50.04 = Number of encoder pulses
As specified on the encoders rating plate
50.03 = CON- ENCODER
The encoder connected to the SDCS-CON-2 board is used for speed control.
Switch ON power.
DANGER: System components now energized!
Start drive.
Increase reference value in LOCAL mode to 10 % of the maximum speed.