25 
     
   
 
Fault Tracing Thyristors 
Converters size D5, D6, and D7 (900...5200 A) 
  These converters are equipped with fuses in the branches of the 
power part. 
  The converter must be disconnected from the mains. 
 
Blown fuses 
 
  In case of a blown fuse, the faulty thyristor or the faulty pair of 
thyristors are already isolated at one side from the others and 
therefore the faulty branch is known (see picture Anti-parallel 
B6-bridges with branching fuses on page 45). 
  The OHM test should be performed, when the thyristor is still 
clamped. Outside the converter a special thyristor clamping 
device is needed. 
  For 4-Q converters with anti-parallel thyristors or BCT’s: 
  The selection of a forward or reverse thyristor or BCT 
(Bidirectional-Controlled-Thyristor) is done during the 
disassembly. Continue with related part Exchange of Thyristors 
for Size D5
, D6 or D7 section Find faulty thyristor. 
  After a thyristor was replaced, the OHM test should be done 
another time to make sure that all faulty thyristors have been 
detected! If the motor is still connected to the converter the 
result of the measurement may be wrong. 
 
Ripple monitor 
  If the ripple monitor fault occurred, a fault tracing as described 
above must be carried out: 
  Check the fuses and the thyristors, according to the statements 
before. 
  If the power section seems to be ok, but still one or more 
thyristors don’t take current, something went wrong in between 
the firing pulse generation and the thyristor’s gate; in this case 
check: 
  Is a firing pulse present on the primary side of the firing 
pulse transformer? 
  Is a firing pulse present on the secondary side of the 
firing pulse transformer? 
  Is the firing pulse transferred to the gate of the thyristor? 
Are there all electrical connections still healthy? 
  Can the thyristor be fired with the applied firing pulse? Is 
the pulse form of the firing pulse identical at all 
measuring positions? 
  Check the settings of the current controller. 
  Check the AC mains network by taking recordings of the line 
voltage and current at all 3 phases at the same time.