For DPA UPScale M-20 kW UPS systems, it is permissible to use 30-50 (only even numbers) 12 V
battery blocks depending the power sourced on the output.
(For more information refer to chapter 6 of the technical data sheet).
IMPORTANT:
For maximum battery autonomies with the corresponding output power range and number of battery
blocks per string, refer to the “battery characteristics” chapter in the technical data sheet.
NOTE:
Set up the correct number of battery blocks in the control panel (menu: Service-Set-Up).
DPA UPScale ST S2 60 FRAME
Module
Module
Module Module Module Module
Module Module Module Module
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
10x7Ah
1x(2x40)x7Ah 2x(2x40)x7Ah 3x(2x40)x7Ah 3x(1x50)x7Ah
Fig 5.5.2-1: Internal Battery Modules DPA UPScale ST S2 60
Other combinations are possible - refer to the technical data sheet.