Endura AZ series integral and remote transmitter
Combustion oxygen monitor 5 Programming
60 IM/AZ20E–EN Rev. F
…Input/Output
Current Output 2 Displayed only if an option board is fitted.
Elec. Range Hi Selects the electrical range high current output value.
[0.00 to 22.00 mA]
mA 20.00 mA
Elec. Range Lo Selects the electrical range low current output value.
[0.00 to 22.00 mA]
mA 4.00 mA
Output Failure When 'Enabled', the current output can be driven to a
preset value if a Failure category diagnostic state
occurs – see Section 8.1, page 78.
Disabled
Enabled
Disabled
Failure Current Sets a preset value that the current output is driven to
when a Failure category diagnostic state is present –
see page 78.
Only available if Output Failure is Enabled.
[0.00 to 22.0 mA]
22.00 mA
Output #2 Test Selects % output levels for Current Output 2.
When this parameter is exited, the current output
returns to its normal operating value.
[0, 25, 50, 75 or 100 %]
0
Parameter Comment / [Range] Default
Table 5.12 Input/Output Menu (Continued)