5 - Installation
During installation do not place the
inverter with the front cover facing
towards the ground.
Position the bracket
01
so that it is
perfectly level on the wall and use it
as a boring template.
Make the 3 holes required, using a
drill with a 10 mm diameter bit. The
depth of the holes should be about
70 mm. On the bracket
01
there are
3 fastening holes.
Fix the bracket to the wall with the 3
wall anchors, 10mm in diameter, sup-
plied. (Step 1).
Hook the inverter to the bracket
springs in correspondence with the
insertion points in the bracket on the
back of the inverter (Step 2).
Drill 2 holes in correspondence with
the slots on the inverter lower bra-
cket, using a drill with a 10 mm dia-
meter bit. The holes must be approxi-
mately 70 mm deep.
Anchor the lower part of the inverter
using No. 2 plugs with a diameter of
10 mm, supplied (Step 3).
Unscrew the 6 screws and open the
front cover
03
in order to make all the
necessary connections.
Do not open the inverter in the
case of rain, snow or a high level
of humidity (>95%)
Once the connections have been
made, close the cover by tightening
the 6 screws on the front to a mini-
mum tightening torque of 1.5 Nm.
Wall mounting