7 - Operation
Display access and settings
Once the inverter has been commissioned, it is possible/necessary to
congure the inverter by accessing the Settings Menu directly from the
display. The following are the main adjustable parameters (see the sec-
tion on “Menu descriptions”)
• RS485 address: setting required in the case of system monitoring via
the RS485 line
• Vstart: setting required if requested by the congurator during the sy-
stem sizing procedure ("Vstart" parameter)
• MPPT scan: allows maximum power point tracking with settable sensi-
tivity and time interval ("MPPT" parameter).
• Reactive power feed-in setting (where present): setting necessary
for managing the different ways of feeding reactive power into the grid
(“Reactive Power" parameter)
Active power limitation setting (where present): setting necessary to
set a limit on the active power supplied by the inverter (“Power reduction”
parameter)