54
000026GG-F
5 - Installation
7mm
4...6mm
7.6...9.3mm
2
4. AMPHENOL H4 quick t connectors
Installation of Amphenol H4 connectors requires crimping to be carried
out with suitable equipment.
- Strip the cable to which you want to apply the connector (after verifying
that it complies with the connector limits).
- Apply the terminal to the conductor using suitable crimping pliers.
Amphenol H4TC0002
- Insert the cable with the terminal into the interior of the connector, until
you hear the click indicating that the terminal is locked inside the con-
nector.
- Firmly tighten the cable gland using the relevant tool to nish the ope-
ration.
2.6÷2.9 Nm